background image

54

Sensor™ PHC Operation and Setup Guide

4. Test the connection by attaching a jumper between pins 7 and 8 on the 9-

pin D subconnector.


If the E08 error disappears, repair the connection between the magnetic
sensor and the lifter interface board.

5. If the error message remains, test the cable and the lifter interface

connector on the PHC:

a. To test the cable, verify the continuity of each wire that connects

the lifter to the PHC.

b. To test the connector on the PHC, place a jumper between pins 7

and 8 of the 9-pin D subconnector.

If the E08 error disappears from the console, the fault is in the cable. If the
error persists, the fault is in the PHC. Contact Technical Support.

Ground connection

Pins 7 and 8

Pins 7 and 8