beautypg.com

Multiple actuator (parallel) wiring – Greenheck S73 Series User Manual

Page 8

background image

Multiple Actuator (Parallel) Wiring

A voltage is present on both motor windings, these voltages

are out of phase and different in magnitude. If these windings

are connected to one another as shown in the INCORRECT

diagrams, this will interfere with the motor performance. Use

a multiple pole switch as shown in the CORRECT diagram.

incOrrect cOnnectiOns

A. No supply on terminal L.

B. Control switch in “Open Run Position”

C. Both actuators in a mid-travel position. i.e. Their open

& close travel switches are closed, allowing them to

operate in an open or close travel direction.

*The following three diagrams show progressive

result of parallel wiring.

D. 120VAC source applied, both motors start to run “open”.

(Shows current flow)

E. #1 actuator runs fully open and its travel limit switch

opens circuit. This actuator stops (perhaps only for a

short time!). #2 actuator continues to run open.

(Shows current flow)

F. The other “Back Feeding” current path existing between

the actuators is shown.

G. Though actuator #1 had come to rest (full open), it can

and does get current flowing through its close travel leg

via this “Back Feeding” current from #2 actuator.

This causes actuator #1 to run a couple of degrees in the

closed direction, #2 actuator will then reach its fully open

position. If left running for a “good” period, both actuators end

up driving each other OPEN-CLOSED at strange positions.

(Shows current flow)

(Shows other “Back Feeding” current flow)

BRAY Series 73 Electric Actuator

Operation and Maintenance Manual

6