Ppendix – Greenheck S73 Series User Manual

Page 14

background image

a

PPenDIx

b

a

ctuatOr

t

rOubleshOOting

c

hart

Problem

Possible cause

Solutions

Actuator does not operate

Cams are depressing travel switch

Adjust cams to their correct positions

Override is engaged/shaft depressed Apply electricity to cancel manual

mode

Wiring is incorrect

Check wiring and power supply

Actuator has reached its thermal

Allow time to cool

shutdown temperature

Actuator operates in reverse

Field wiring is reversed

Rewire field wiring

directions
Actuator does not fully close valve

Limit switches are tripping

Readjust travel limit switches

(or open valve)

Valve torque requirement is higher

Manually override out of seat, try

than actuator output

angle seating or fit larger actuator

Voltage power supply is low

Check power source

Motor hums but does not run

Motor brake engaged

Check that brake is not obstructed

Corrosion inside unit

Condensation forming

Test heater wiring, should have

constant power supply

Water leaking into the unit

Check all seals and possible water

entry through conduit

BRAY Series 73 Electric Actuator

Operation and Maintenance Manual