Mode 3: IDC Single Normally-Closed (N.C.) Switch

In this configuration, only one normally-closed dry contact closure may be installed per supervised line.
In this mode, the loop is monitored for open circuits, wire-to-wire short circuits (across + and –), and
ground faults. When the contact closure is not active (closed), the 15 k

 is bypassed and the circuit sees

only the 5.1 k

 load.

Figure 6. IDC Single Normally-Closed Switch

This change is sensed by the MRM and indicates to the MRM that the contact closure is active. If there is
a short across L1 and L2, if either leg is grounded, or if a break occurs on either leg, the MRM indicates
that a fault has occurred.

N

OTE

: The terminating resistors are not included with the MRM. These resistors are included in a kit

(12509-004), which must be ordered separately.