Installation, Mounting, Wiring – GAI-Tronics 379-002 Monitored RElay Module (MRM) Stations User Manual

Page 3: Power

background image

Pub. 42004-491A

Model 379-002 Monitored Relay Module Station

Page 3 of 13

f:\standard ioms - current release\42004 instr. manuals\42004-491a.doc
03/14

Installation

CAUTION

Do not install this equipment in hazardous areas. Disconnect power before installing or removing
the MRM.

Mounting

The Model 379-002 MRM Station enclosure is not supplied with conduit or cable gland holes since cable
quantity, size, and entry location vary with each installation.

Drill or punch openings at the required locations before mounting the enclosure. Typically multiple
cables entries are required for power, serial data line, and input wiring. Refer to the Wiring section
below. Use caution when drilling or punching the enclosure to avoid damaging the internal components.
Bottom cable entry is recommended to prevent moisture from entering the enclosure and dripping onto
the terminals or circuit boards.

Mount the enclosure to a suitable surface using appropriate customer-supplied hardware. Refer to Figure
1 for mounting hole dimensions.

Remove the shipping tie-wrap that is securing the PCBA to its mounting Snaptrack.

Wiring

The MRM Station requires 120 V ac power and a serial data line connection (RS-485) to the ADVANCE
System Control Cabinet. Up to eight input and relay output circuits are connected as needed. Each
connection is explained below.

Power

120 V ac power is connected to terminal block TB13 at the top of the panel. Refer to Figure 1.

WARNING

Insure proper grounding to protective earthing.

Earth grounding provisions are provided.

Table 1.

Function Terminal

Block Wire

Color

AC Line (hot)

TB13-1

Black

Neutral TB13-2

White

Ground TB13-3 Green/yellow