Menu Control
– continued –
Blowdown valve
Note
For more information on the
operating position of the continuous blowdown valve,
24hours purging pulse (conductivity control) and CANopen actuator see chapter
Glossary page 42.
Concerning:
■
Conductivity control LRG x-4x and LRR -40
. To set the individual parameters press button
. The activated item is shown in the symbol
bar.
2. To select the CANopen actuator turn the
navigation wheel and confirm the input by
pressing the navigation wheel. The background
of the selected item is flashing.
3. Turn the navigation wheel to select YES if the
continuous blowdown valve is fitted with a
CANopen actuator or NO if it is equipped with
another type of actuator.
4. Press the navigation wheel. The flashing stops.
5. To calibrate the continuous blowdown valve turn the navigation wheel to the first value to be
adjusted.
6. Press the navigation wheel. The background of the selected item is flashing.
7. Turn the navigation wheel to the left or to the right. The valve closes or opens.
8. Press the navigation wheel to stop the valve. The position of the valve is shown in the display.
9. If necessary correct the valve position by turning the navigation wheel.
0. Once the desired position of the valve has been established press button
to calibrate the
equipment. The value is accepted and the flashing stops.
. For the second calibration repeat items 5 to 0 and finish the input by pressing button
.
2. After the calibration procedure the current position of the continuous blowdown valve will be
indicated in the display.
3. To set further parameters press button
. The activated item is highlighted in the symbol bar.
4. To set the desired parameter turn the navigation wheel and confirm the input by pressing the
navigation wheel. The background of the selected item is flashing.
5. To enter a new value turn the navigation wheel and confirm the selection by pressing the
navigation wheel. The flashing stops.
6. To obtain more available elements repeat items 3 to 5 and press button
.
Device name
Temperature
Blowdown valve
MIN/Blowdown
020%
0%
100%
Operating position: 000 %
24h-rinsing:
OFF
CANopen actuator: NO