Operation – Flowserve URB 2 User Manual
Page 14

4
Operation
– continued –
Menus
The start window in the display shows all possible indications and readings. Note that the system
configuration determines what is actually indicated.
Level controller NRR 2-40, manual operation, level
45 %
Conductivity controller LRR-40, manual operation*)
Conductivity controller LRR-40, stand-by operation*)
Conductivity MAX limit setting 6000 μS/cm
Conductivity Actual value setting 4800 μS/cm
Temperature MAX limit setting 300°C
Temperature Actual value 50°C
*) Both indications at the same time are not possible
during operation.
. To select a menu turn the navigation wheel to the
left or right. The selected menu is highlighted in
the title bar and the overview display of the menu
is indicated.
2. To call up the selected menu press the navigation
wheel.
3. To select the value to be set or the equipment in
question turn the navigation wheel. The selection
will be highlighted.
4. To call up the menu of the parameter or equipment
press the navigation wheel. The selected menu will
be shown.
5. Only applicable for the menu Control: To get the full
listing of all devices repeat items 3 and 4.
■
Press button
to quit the currently active menu.
Home
Control
Limiter
Level
45 %
Conductivity
StdBy
MAX 6000
ACT. 4800 µS/cm
Pressure
MAX
ACT.
bar
Temperature
MAX
300
ACT.
150 °C
Function
NRG 16-42 - Level
NRG 26-40 - Level
LRG 1x-4x - Conductivity
TRV 5-40 - Temperature
Status
ON
ON
ON
ON
Home
Control
Limiter
Home
Control
Limiter
Choice