Limitorque Worcester Controls CEA Series FCD WCENIM2080-00-AQ 12/14

flowserve.com

C-MOD version

The C-MOD or Modulating control actuator ships from the factory
calibrated and ready to operate. It is not necessary to remove the Con-
trols Cover if factory settings are suitable. Wire the actuator according
to the wiring diagram located inside the Terminal Block cover.

Key default settings include:

• Factory calibrated for 0-90 degree operation

• Direct Acting CCW to Open

• L1 and L2 are for input voltage 120 or 240VAC (Consult Factory for

other AC/DC voltages)

• Terminals 11, 12, 13 and 14

- Terminal 11 = + 4-20mA current source (input)
- Terminal 12 = ( - ) 4-20mA current source (input)
- Terminal 13 = + Loop Powered 24VDC + 4-20mA current
(output)
- Terminal 14 = ( - ) Loop Powered 24VDC + 4-20mA current
(output)

• Terminals 1 and 2 are Normally Open (NO) dry relay contacts for

OUTPUT 1 (CCW)

• Terminals 3 and 4 are Normally Open (NO) dry relay contacts for

OUTPUT 2 (CW)

• Terminals 5 and 6 are Normally Open (NO) dry relay contacts for

OUTPUT 3 (Torque or MID)

• Terminals 7 and 8 are Normally Open (NO) dry relay contacts for

OUTPUT 4 (Compartment Temp)

NOTE: L1 and L2 are to be powered at all times

NOTE: 4-20mA output is to be loop powered with 24VDC.
Voltage range 13-24VDC.

2.1 C-MOD Wiring

NOTE 1: Contact rating = 16amp @ 250VAC, dry contact. All outputs

are programmable, remote voltage inputs are 12VDC

to 240VAC for Open, Closed, Mid/Dribble terminals

(20,21,22,23)