flowserve.com
Basic Menu Calibrate/Outputs/Alarms/Compartment Temp
>>>> ON/OFF
 
Min temp
>>>> -5
Max temp
>>>> 125
 Hysteresis
 
Alarm out
>>>> ON
All (4) four relay outputs are configured in the same manner. Below is 
a list of the parameters.
Alm dev
Alm Lim 1
Alm Lim 2
Alm Torque
Alm mtrtmp
cmptmp
The default outputs are as follows:
OUTPUT 1= CCW (activates upon full CCW travel. NOTE: normally 
open dry contact closes)
OUTPUT 2=CW (activates upon full CW travel. NOTE: normally open 
dry contact closes)
OUTPUT 3 = TORQUE (activates when torque is below the low limit or 
above the high limit NOTE: normally open dry contact closes)
OUTPUT 4 = COMPARTMENT TEMPERATURE (activates when torque 
is below the low limit or above the high limit. NOTE: normally open 
dry contact closes)
Setting the dome indicator and internal magnet puck inside the 
controls cover
4.10 Positioner Indicator
High visibility position indicator is standard with each actuator. 
Indicator rotation is accomplished using high performance neodym-
ium magnets that eliminate cover shaft holes and potential path for 
moisture ingress. 
Indicator is self-indexing and does not require removal to remove the 
top cover.
Dome Indicator Adjustment
The dome indicator will come preset from the factory. The indicator 
will display CLOSED in the clockwise (CW) position in the viewing 
window. The indicator dome may be rotated 90
o
to display OPEN in
the CW position.
The dome indicator also has adjustment slots to further align the OPEN 
and CLOSED display after the controls cover is completely tightened 
down. Loosen the 4 pan head screws that hold down the dome and 
rotate CW or CCW as needed. The screws holding down the dome 
should only be loosened (not removed) to ensure that the O-ring under 
the dome is not pinched when the screws are re-tightened.