Explanatory Notes

– continued –

Function

– continued –

n

Temperature compensation NORM: The conductivity/temperature curves of normally used

conditioning agents are stored in the electrode and can be selected.

The standard curve temperature compensation is suitable for boilers operating with variable pressure,

which means that the boiler does not have a fixed working pressure (e.g. low load 0 bar, full load

5 bar). The standard curves of feedwater conditioning agents with different basic conductivities com-

pensate for the influence of the temperature on readings within the operating range.

n

Temperature compensation LINEAR: A fixed temperature coefficient (Tk) is used to correct the

measured conductivity value linearly.

The gradient (default setting: . % / °C) is normally used for steam boilers operating with constant

pressure. The conductivity is ascertained at an ambient temperature of 5°C. The cell constant can

be modified in order to calibrate the value measured by the electrode. The gradient can be verified at

operating pressure with the aid of a calibrated conductivity meter.
At regular intervals the conductivity electrode LRG x-40 sends a data telegram via CAN-bus to the

controller with the following information:

n

Measured conductivity value, referred to 5°C as actual value (X),

n

Measuring range / adaptation of actual value output,

n

Alarm: self-monitoring of electrode supply cables,

n

Alarm: temperature sensor defective,

n

Alarm: excessively high temperature in terminal box.

A short circuit in the cables leading to the measuring electrode, the measuring tube and the resistance

thermometer or the interruption of the data transmission via CAN bus will be indicated by a malfunc-

tion message.
A sensor monitors the temperature in the terminal box and indicates a malfunction if the limit value is

exceeded.

System components

Design

LRG 1x-40

Screwed ", ISO 8-.

Fig. 3, Fig. 4

LRR 1-40

Digital switching controller for conductivity electrode LRG x-40

Functions: Conductivity limiter, continuous blowdown controller

Data exchange via CAN bus to ISO 898 using CANopen protocol
URB 1, URB 2

Operating & display unit

Functions: Parameterization, indication via LCD display

Data exchange via CAN bus to ISO 898 using CANopen protocol