beautypg.com

Wiring – Flowserve LRG 16-40 User Manual

Page 20

background image

0

Wiring

Bus cable

Use screened multi-core twisted-pair control cable – e.g. UNITRONIC

®

BUS CAN x x...mm

or

RE-YCYV-fl x x...mm

as bus cable or the preassembled control cable that is available as

accessory.
The baud rate (data transfer rate) dictates the cable length between the bus nodes, and the total power

consumption of the sensor dictates the conductor size.

The baud rate is set via code switches

3 (S8 to S0), Fig. 6. Default factory setting of conductivity

electrode LRG x- 40: baud rate 50 kbit/s (cable length 5 m).
For longer cable lengths reduce baud rate accordingly. Make sure that all bus nodes feature the same

settings.

S 8

S 9

S 10

Baud rate

Cable length

Number of pairs and

conductor size [mm

2

]

OFF

ON

OFF

250 kBit/s

125 m

x x 0.34

Factory setting

ON

ON

OFF

5 kBit/s

50 m

x x 0.5

OFF

OFF

ON

00 kBit/s

335 m

x x 0.75

ON

OFF

ON

50 kBit/s

500 m

available on demand

(depends on bus configuration)

OFF

ON

ON

0 kBit/s

000 m

ON

ON

ON

0 kBit/s

000 m

Note

The max. baud rates and cable lengths indicated above are based on empirical values

obtained by GESTRA. In certain cases it may be necessary to reduce the baud rate in

order to ensure operational safety.
The design and preparation of the data cable is an important factor for the electro-

magnetic compatibility (EMC) of the equipment. Wiring should therefore be carried out

with special care.

If you do not use the preassembled control cable, connect the connector and the jack for the CAN bus

lines according to the wiring diagram.

Assigning the connector and jack

UNITRONIC

®

is a registered trademark of LAPP Kabelwerke GmbH, Stuttgart.

This manual is related to the following products: