5

Systematic malfunction analysis

The sources of malfunctions occurring in CAN bus systems operating with several bus-based stations

must be analysed systematically since faulty components or incorrect settings can give rise to

negative interactions with intact bus devices in the CAN bus system. These unwanted interactions

can cause error messages in fully functional bus devices, which will make fault detection even more

difficult.
We recommend the following systematic fault finding procedure:

System Malfunctions

– continued –

Step 1 (Start)

Detach terminal strips

in all sensing units of

bus devices.
Level electrode

Conductivity electrode

Pressure sensor

Temperature sensor

etc.

Step 3

Apply mains voltage

to bus devices

of the system

e. g. NRS ...

and

NRG ...

Step 2

Plug in terminal strips

of the sensing unit

of one system

e. g. NRS ...

and

NRG ... (electrodes)

System O.K.

Detach terminal strips

between bus devices

of the system

e. g. NRS ...

and

NRG ...

System
Malfunction

Use fault-finding

list to identify

the fault(s)!

Cut off power supply

to the equipment!

Check

Use fault-finding

list to correct

fault(s)!

Final test:

Have all faults

been eliminated?

Check next system