Malfunctions – Flowserve LRG 16-40 User Manual

Page 26

background image

6

Malfunctions

Fault finding list for troubleshooting

Equipment does not work

Fault:

No voltage supply, no function.

Remedy: Check voltage supply and wiring.

Fault:

The electronic circuit board is defective.

Remedy: Replace electronic circuit board.

Only the red LED 2 is flashing

Fault:

Conductivity electrode defective (internal connecting wires are short circuited or

interrupted, insulating seal defective).

Remedy: Replace conductivitiy electrode.

Fault:

Measuring surface of conductivity electrode is exposed.

Remedy: Check installation and make sure that the measuring surface is submerged.

Fault:

The measuring surface is contaminated and therefore an incorrect actual value is indicated

(ascertained by reference measurement).

Remedy: Remove conductivity electrode and clean measuring surface.

Fault:

Dirt deposits on the measuring surface cause MAX or MIN alarms although the actual value

is between these limits (reference measurement).

Remedy: Remove conductivity electrode and clean measuring surface.

Fault:

The earth connection to the vessel is interrupted. No function.

Remedy: Clean seating surfaces and screw in the equipment together with the supplied joint ring

∅ 33 x 39, form D, DIN 7603 (material: .430, bright-annealed). Do not insulate the

electrode with hemp or PTFE tape!

Green LED 1 and red LED 2 are flashing alternately

Fault:

The thermal fuse has been triggered.

Remedy: Check installation. The ambient temperature must not exceed 70°C. As soon as the tem-

perature falls below the max. admissible limit, the equipment switches back to operating

mode.

Fault:

The fluid temperature sensor is either short circuited or interrupted.

Remedy: Replace conductivitiy electrode.