Flowserve PMV D3 Digital Positioner User Manual
Page 24

24
Actuator
Type of actuator
Size of actuator
Time out
Rotating
Rotating actuator.
Small
10 s
Linear
Linear actuator.
Medium
25 s
Large
60 s
Texas
180 s
Lever
Only for linear actuator.
  Lever stroke Stroke length to achieve correct display.
 Level cal
Calibration of positions to achieve correct display.
Direction
  Direct
Direct function (signal increase opens). Indicator/spindle rotates counter-clockwise.
Reverse
Reverse function.
Character
Curves that show position as a function of input signal.
 Linear
  Equal %
See diagram.
 Quick open
 Sqr root
 Custom
Create own curve.
Cust chr
 # of point
Specify number of points (3, 5, 9,
17, or 33)
Cust curve Enter values on X and Y axes.
Curr range
 0%=4.0 mA
 100%=20.0 mA
Possibility of selecting which input signal values will correspond to
0% and 100% movement respectively. Examples of settings:
4 mA = 0%, 12 mA = 100%, 12 mA = 0%, 20 mA = 100%.
FULL MENU
SETUP
The Setup Menu is used for various settings.
The menu contents are shown in the chart on the next page and the various texts are
described below:
Qo
Sqr
Lin
Eq%
Signal
Movement
x
y