User Instructions - Digital Positioner 3200MD LGENIM0059-09 12/13
5
Table VII: Hazardous Area Certifi cations
North America (FM/CSA)
Flame Proof
SIRA 03ATEX1387
II 2 GD
Ex d IIB+H2 T5 IP65
Ex tD A21 IP65 T95˚C (Ta =-40°C to +80°C)
T5 (Ta = -40˚C to +80C
Explosion Proof
Class I, Div 1, Groups B,C,D
DIP Class II, III, Div 1 Groups E,F,G
Class I, Zone 1, Ex d IIB+H2 (CSA Only)
T5 Tamb = -40˚C ≤ Ta ≤ +80˚C (CSA Only)
T6 Tamb = -40˚C ≤ Ta ≤ +60˚C
Type 4X
Intrinsically Safe
SIRA 03ATEX2299X
II 1 GD
Ex ia IIC Ex iaD 20 T95˚C
T4 (Ta = -52˚C to +85˚C) (Ta = -52˚C to +80˚C)
T5 (Ta = -52˚C to +55˚C)
Entity Parameters
Ui = 30V
Ii = 100mA
Pi = 800mW
Ci = 30nF Co = 36nF
Li = 0
Intrinsically Safe
Class I,II, III, Div 1, Groups A,B,C,D,E,F,G
Class I, Zone 0, AExia IIC (FM Only)
T4 Tamb = -50˚C ≤ Ta ≤ +85˚C
T5 Tamb = -50˚C ≤ Ta ≤ +55˚C
Type 4X
Entity Parameters
Ui = 30V
Ii = 100mA
Pi = 800mW
Ci = 30nF
Li = 0
Non-Incendive
SIRA 08ATEX4006
II 3 GD
Ex nL nA IIC
Ex tD A22 T95˚C (Ta = -52°C to +80°C)
T4 (Ta = -52˚C to +85˚C)
T5 (Ta = -52˚C to +55˚C)
Non-Incendive
Class I, Div 2, Groups A,B,C,D
T4 Tamb = -50˚C ≤ Ta ≤ +85˚C
T5 Tamb = -50˚C ≤ Ta ≤ +55˚C
Type 4X
Barriers Not Required
IECEx
InMetro
Explosion Proof
IECEx SIR 04.0023X
Ex d IIB+H2 T5
Ta = -40˚C to +55˚C
Explosion Proof
TÜV 11.0070
Ex d IIB+H2 T5 Gb IP65
Ta = -40˚C -Ta - +80˚C
Intrinsically Safe
IECEx FMG 05.0003X
Ex ia IIC Ex iaD 20 T95˚C
T4 Ta = -40˚C to +85˚C Ta = -40C to +80˚C
T5 Ta = -40˚C to +55˚C
Entity Parameters
Ui = 30V
Ii = 100mA
Pi = 800mW
Ci = 30nF
Li = 0
Instrinsically Safe
TÜV 11.0071X
Ex ia IIC Ga IP65 Ex ia IIIC T95˚C Da IP65
T4 Ta = -40˚C-Ta- +85˚C Ta = -40˚C-Ta- +85˚C
T5 Ta = -40˚C-Ta- +55˚C
Entity Parameters
Ui = 30Vcc
Ii = 100mA
Pi= 800mW
Ci = 30nF
Li = 0
KOSHA
Gost
Explosion Proof
10-AV4BO-0560X
Ex d IIB+H2 T5
T5 Ta = -20°C to +50°C
Special Conditions for Safe Use:
•
The equipment must be installed in such a manner as to minimize the risk of impact or friction with other metal surfaces.
•
To avoid possibility of static discharge clean only with a damp Cloth
•
In order to maintain the explosion proof certifi cations do not remove or loosen covers while circuits are live.
•
For Intrinsically Safe installations the positioner must be connected to suitably rated intrinsically safe equipment, and must be installed in accordance
with intrinsically safe installation standards.
•
Substitution of components may impair Intrinsic Safety.