2 maintenance schedule – Flowserve LNGT User Manual
Page 29

LNGT USER INSTRUCTIONS ENGLISH 00083107 02-08
Page 29 of 48
®
Before restarting the machine, the relevant 
instructions listed in section 5, Commissioning, 
start up, operation and shut down must be 
observed. 
 
Oil and grease leaks may make the ground 
slippery. Machine maintenance must always 
begin and finish by cleaning the ground and the 
exterior of the machine. 
 
If platforms, stairs and guard rails are required for 
maintenance, they must be placed for easy access 
to areas where maintenance and inspection are to 
be carried out. The positioning of these 
accessories must not limit access or hinder the 
lifting of the part to be serviced. 
 
When air or compressed inert gas is used in the 
maintenance process, the operator and anyone in 
the vicinity must be careful and have the 
appropriate protection. 
 
Do not spray air or compressed inert gas on skin. 
 
Do not direct an air or gas jet towards other people. 
Never use air or compressed inert gas to clean 
clothes. 
 
Before working on the pump, take measures to 
prevent an uncontrolled start. Put a warning board 
on the starting device with the words: 
"Machine under repair: do not start". 
 
With electric drive equipment, lock the main switch 
open and withdraw any fuses. Put a warning board 
on the fuse box or main switch with the words: 
"Machine under repair: do not connect". 
 
Never clean equipment with inflammable solvents 
or carbon tetrachloride. Protect yourself against 
toxic fumes when using cleaning agents. 
 
6.2 Maintenance schedule
It is recommended that a maintenance plan
and schedule is adopted, in line with these User 
Instructions. It should include the following: 
a) Any auxiliary systems installed must be 
monitored, if necessary, to ensure they function 
correctly. 
b) Gland packings must be adjusted correctly to
give visible leakage and concentric alignment 
of the gland follower to prevent excessive 
temperature of the packing or follower. 
c) Check for any leaks from gaskets and seals.
The correct functioning of the shaft seal must 
be checked regularly. 
d) Check bearing lubricant level, and if the hours
run show a lubricant change is required.
e) Check that the duty condition is in the safe
operating range for the pump.
f) Check vibration, noise level and surface
temperature at the bearings to confirm 
satisfactory operation. 
g) Check dirt and dust is removed from areas
around close clearances, bearing housings and 
motors. 
h) Check coupling alignment and re-align if
necessary.
 
Our specialist service personnel can help with 
preventative maintenance records and provide 
condition monitoring for temperature and vibration 
to identify the onset of potential problems. 
 
If any problems are found the following sequence 
of actions should take place: 
a) Refer to section 7, Faults; causes and 
remedies, for fault diagnosis.
b) Ensure equipment complies with the
recommendations in this manual.
c) Contact Flowserve if the problem persists. 
 
6.2.1 Routine inspection [daily/weekly] 
The following checks should be
made and the appropriate action taken to remedy 
any deviations: 
a) Check operating behavior. Ensure noise, 
vibration and bearing temperatures are normal.
b) Check that there are no abnormal fluid or
lubricant leaks [static and dynamic seals] and 
that any sealant systems [if fitted] are full and 
operating normally. 
c) Check that shaft seal leaks are within
acceptable limits.
d) Check the level and condition of oil lubricant.
On grease lubricated pumps, check running 
hours since last recharge of grease or 
complete grease change. 
e) Check any auxiliary supplies eg
heating/cooling, if fitted, are functioning 
correctly. 
Refer to the manuals of any associated
equipment for routine checks needed. 
 
