2 suction piping – Flowserve LNGT User Manual
Page 19

LNGT USER INSTRUCTIONS ENGLISH 00083107 02-08
Page 19 of 48
®
 
4.4.2 Suction piping 
Refer to the diagrams below for typical designs of 
suction piping for both flooded suction and 
suction lift. 
a) The inlet pipe should be one or two sizes 
larger than the pump inlet bore and pipe 
bends should be as large a radius as 
possible. 
b) Pipe work reducers should be conical and
have a maximum total angle of divergence of 
15 degrees. 
c) On suction lift the piping should be inclined
up towards the pump inlet with eccentric 
reducers incorporated to prevent air locks. 
d) On positive suction, the inlet piping must
have a constant fall towards the pump.
e) Flow should enter the pump suction with
uniform flow, to minimize noise and wear. 
This is particularly important on large or high-
speed pumps which should have a minimum 
of five diameters of straight pipe on the pump 
suction between the elbow and inlet flange. 
See section 10.3, Reference 1, for more 
detail. 
f) Inlet strainers, when used, should have a net
`free area' of at least three times the inlet pipe 
area. 
g) Do not install elbows at an angle other than
perpendicular to the shaft axis. Elbows 
parallel to the shaft axis will cause uneven 
flow. 
h) Except in unusual circumstances strainers
are not recommended in inlet piping. If 
considerable foreign matter is expected a 
screen installed at the entrance to the wet 
well is preferable. 
i)
Fitting an isolation valve will allow easier 
maintenance. 
j)
Never throttle pump on suction side and 
never place a valve directly on the pump inlet 
nozzle. 
 
Typical design – flooded suction 
Discharge 
isolating 
valve 
Non 
return 
valve 
Concentric 
conical 
reducer 
Eccentric 
conical 
reducer 
Suction 
isolating 
valve 
Slope up from 
pump suction 
Note: 
Ideally reducers should be limited to one pipe diameter 
change, 
ie 150 mm [6 in.] to 200 mm [8 in.]. Must have a maximum 
total angle of divergence of 15 degrees. 
 
 
Typical design – suction lift 
L o n g 
r a d i u s 
b e n d 
S l o p e d o w n 
f r o m p u m p 
s u c t i o n 
>5D
E c c e n t r i c 
c o n i c a l 
r e d u c e r 
D i s c h a r g e 
i s o l a t i n g 
v a l v e 
C o n c e n t r i c 
c o n i c a l 
r e d u c e r 
N o n 
r e t u r n 
v a l v e 
Notes: 
1. S = Minimum submergence >3E. 
2. Ideally reducers to be limited to one pipe diameter change, 
ie 150 mm [6 in.] to 200 mm [8 in.]. Must have a maximum 
total angle of
divergence of 15 degrees.
>5D
