4) connection 5) installer commissioning, 6) use, 7) alarm – Delta Dore T1D DIGIT User Manual

Page 2: User mode

background image

4) Connection

5) Installer commissioning

Place the switch in the PROG position.

Press the

or

buttons to display the required value.

Press

to accept and go to the next parameter.

If the safety setpoint is "Off", setpoint 3 is not displayed.

When all the settings have been defined, the switch

must be returned to the

position.

PROG

6) Use

T1D digit continuously compares the
temperature measured by probe 1 with
the temperature measured by probe 2.

If T° probe 1 - T° probe 2 > maximum
difference the output switches to On.

If T° probe 1 - T° probe 2 < minimum
difference the output switches to Off.

The safety setpoint (e.g. 5 °C frost protection) is used to "force"
the output to On in the case where the temperature measured
by probe 3 falls below this setpoint.

User mode

T1D digit continuously displays the measured temperature.
You can display all the measured temperatures
by pressing the

button repeatedly:

probe 1, probe 2 or probe 3.

7) Alarm

The "Alarm" warning light flashes to indicate that a fault has occurred.

N

L

7 8 9 1011

T1D digit

Control
(e.g. Circulator)

Probe 1 : Highest temperature

(collection source)

Probe 2 : Lowest temperature

(storage, e.g. hot water tank)

Probe 3 : Safety temperature (e.g. outside T˚)

PROG

1 2

Probe 1

3 4

Probe 2

5 6

Probe 3

N L

230 V~

50 Hz

230 V~

5A max

PROG

Function no.

Description

Maximum difference

From + 3.5 ˚C to + 30 ˚C in 0.5 ˚C steps

Minimum difference

From + 0.2 ˚C to + 3 ˚C in 0.1 ˚C steps

+ 7˚C

Setting

Default value

+ 2˚C

Safety setpoint

From 0 (Off) to + 90 ˚C in 1 ˚C steps

Off

From - 2 ˚C to + 2 ˚C in 0.5 ˚C steps

From - 2 ˚C to + 2 ˚C in 0.5 ˚C steps

0˚C

From - 2 ˚C to + 2 ˚C in 0.5 ˚C steps

0˚C

0˚C

Probe 3 correction

Probe 1 correction

Probe 2 correction

For clarity, only schematic diagrams are given here. They do not show the protective
devices and other accessories required by the standards.
- The UTE C15-100 standard and good practice must be complied with.
- Connected or adjacent appliances must not generate excessive interference
(directive 89/336/EEC).

Temperature

probe 1

Temperature

probe 2

On

Output
state

Off

Minimum
difference

Maximum
difference

Problem

Diagnosis / Solution

The probe is cut off
Check the probe or its connection.

The probe is short-circuited
Check the probe or its connection.

There is a problem inside the thermostat
Switch off, then switch on again.
If the problem persists, contact the installer.

When the measured
temperature is
consulted, the
thermostat displays:

When the measured
temperature is
consulted, the
thermostat displays:

The temperature display is correct,
but the "Alarm" light is flashing.