Menu 2 – Delta Dore 257 TYBOX Installation User Manual
Page 4
>5s
1
0
EXIT
1
2
3
4
5
1
0
MENU 2
: 5°C --> 30°C
19°C
: 5°C --> 30°C
16°C
0,2°C <
< 2°C
Hysteresis
0,4°C
Permission to change
Programme and settings
0 : Modifications permitted to
programme and settings
1 : Modifications to programme
not permitted and adjustment of
settings limited
+/- 3°C either side of the last
setting.
Tybox 157
Tybox 257
X
X
: 5°C <
< 30°C
: 5°C <
< 16°C
16°C <
< 22°C
13°C <
< 19°C
5°C <
< 11°C
+/- 3°C
PROG
Temperature displayed in AUTO mode
0 : Continuous display of the
temperature setting.
In this case, press the
i
button to display the room temperature
1 : Continuous display of the room
temperature.
In this case, press the
i button to display
the temperature setting.
Tybox 157
Tybox 257
X
Control time base
If you choose an "on/off" type
setting, you can adjust the
hysteresis (or differential) via
menu 2-11
Minutes
Minutes
Minutes
Minutes
On/Off
Automatic time change
(summer/winter time)
Tybox 157
Tybox 257
X
X
Time display mode
12h-24h
Tybox 157
Tybox 257
X
X
24 h
12 h
Measured temperature correction
(-5°C à +5°C par pas de 0,1°C).
Example: If the temperature displayed
on the device is 19°C and the
observed temperature is 20°C,
adjust the temperature by +1°C, then
confirm by pressing OK.
Tybox 157
Tybox 257
X
X
- 5°C <
< +5°C
Before changing this setting,
the device must have been in
operation for at least 2 hours.
Inter val before maintenance of the
boiler(réglable de 0 à 365 jours).
Reprogramme after each
maintenance operation
--- (0) to 365 days
Temperature settings controlled by the transmitter
Reset operating counter hours
of the boiler
Tybox
157
Tybox
257
X
X
No
Yes
Press button 2.
To change the different settings, press
the + or - buttons, then press the OK button
to confirm and move on to the next setting.
Turn the selector dial to
,
then press the
i button for 5
seconds.
Presence of transmitter
Tybox 157
Tybox 257
X
No
Yes