Power Installation
Only a qualified individual should terminate power and signal cable at this
Daktronics display.
The Daktronics engineering staff must approve any changes made to the display.
Before altering the display, submit detailed drawings for the proposed modifications
to the Daktronics engineering staff for evaluation and approval or the warranty will
be rendered null and void.
Schematic, Power Term Panel, 2 Circuit-120/240VAC ............................................. Drawing A-211947
Schematic, Power Term Panel, 1 Circuit-120VAC .................................................... Drawing A-211950
Schematic, Power Term Panel, 2 Pole-240VAC ....................................................... Drawing A-218666
Schematic, Power Term Panel, 1 Pole-240VAC ....................................................... Drawing A-220287
Schematic, AF-3400-12-RGB-P, General ................................................................. Drawing A-253685
Power Specs, AF-3400-(24x192-96-192-12-RGB ..................................................... Drawing A-254277
3.1 Preparing for Power Connection
• A power termination box is provided on the back of the display. If the installation of the
display does not allow for the use of this enclosure, refer to Section 3.6 for information
on the internal wiring for the power.
• Route power to the display through a fused disconnect switch capable of opening all
ungrounded power conductors. Install this disconnect within the line-of-sight of any
personnel performing maintenance on the display. If the disconnect is located out of
sight of the display, it must be capable of being locked in the open position.
Note: Displays are equipped with supplemental protection devices that carry a UL1077
(IEC 60947, VDE 660) rating. These devices are only intended to protect the components
within the display. Suitable devices must be used for the equipment and feeders
supplying power to the display.
• Power conductors from the disconnect to the display should be routed through conduit
in agreement with local code.
• Display power will terminate to the display at the external power termination J-box
mounted to the back of the display.
• Connect the grounding electrode conductor at the grounding lug on the display at this
time.
3.2 Conduit
Daktronics does not include the conduit. Separate conduit must be used to route:
•
Power
•
Signal IN wires to the display, when applicable
Electrical Installation