Electrical Installation

3-4

Figure 12: Installation with Ground and Neutral Conductor Provided

Installation with Only a Neutral Conductor Provided
Installations where no grounding conductor is provided must comply with article 250-32 of
the National Electrical Code. If the installation in question meets all of the requirements of
article 250-32, the following guidelines must be observed:

· Connect the grounding electrode cable at the local disconnect, never at the display panel

board.

· A disconnect that opens all of the ungrounded phase conductors should be used.

· The neutral and the ground conductors should be bonded in the display panel board.

Refer to Figure 13 for installation details.

Figure 13: Installation with only Neutral Conductor provided