Troubleshooting, Signal converter – Daktronics Fiber Optic Communication User Manual

Page 12

background image

Troubleshooting

Signal Converter

The following table gives the typical state of the signal converter when the LEDs are
either on or off. Refer to

Figure 10

for an illustration of the signal converters and the

locations of the various components.

LED

Indicators

Typical States

Troubleshooting

ON

Signal Converter (SC) is receiving
Power

SC is not receiving power

Power

OFF

Internal 1 AMP fuse is bad

Replace SC

SC is not connected to a serial port

Connect to open computer COM

port

On Steady

1. Serial port or serial cable is bad
2. Computer COM port in sleep mode

1. Try another port or replace

serial cable

2. Communicate to display

OFF Steady

Normal state, SC is not transmitting
data

TX

Brief Flicker

SC is transmitting data

ON Steady

1. Field Cabling between SC and

display is bad

2. Connected to display output jack or

terminated incorrectly

3. Bad COM port on display controller

1. Eliminate cabling by

disconnecting wire/cable from
SC to display controller

2. Check connections and

terminations

3. Eliminate by disconnecting

wire/cable to display controller

OFF Steady

Normal state, SC is not receiving data

RX

Brief Flicker

SC is receiving data

TX/RX

ON Steady

(If serial cable is connected) Bad SC

Replace SC

Fiber Signal Converter (0A-1127-0256)
The following tables give the jack pin-outs for a fiber signal
converter.

Figure 10: RS232/Fiber Signal

Converter

J1 - 25 Pin DB-F

PIN

OPERATION

2 TX-P

(out)

3 RX-P

(in)

7 GND

JACK

OPERATION

J2 TX1

(out)

J3 RX1

(in)

J4 TX2

(out)

J5 RX2

(in)






Fiber Optic Communication Manual