Cabling considerations – Contemporary Control Systems BASremote Installation Guide User Manual
Page 9

TD040300-0II
9
C
ABLING
C
ONSIDERATIONS
When attaching cables to the BASR, Table 1 should be considered.
Function Signalling &
Data Rate
Minimum Required
Cable
Maximum
Segment Distance
Ethernet
10BASE-T
10 Mbps
Category 3 UTP
100 m (328 ft)
Ethernet
100BASE-TX
100 Mbps
Category 5 UTP
100 m (328 ft)
I/O
Unspecified
18 AWG
Unspecified
Expansion Unspecified
Belden
®
9841 or equivalent 100 m (328 ft)
Modbus
2.4–115.2 kbps Belden
®
9841, 3106A, 9842 100 m (328 ft)
Table 1 — Cabling Considerations
NOTE: If using shielded cable, connect to chassis at only one point. Wire
size may be dictated by electrical codes for the area where the equipment is
being installed. Consult local regulations.
Observe in Table 1 that 10BASE-T segments can successfully use Category 3,
4 or 5 cable — however, 100BASE-TX segments must use Category 5 cable.
Category 5e cable is highly recommended as the minimum for new installations.
The Ethernet port of the BASR employs Auto-MDIX technology so that either
straight-through or crossover cables can be used to connect to the network.