Cabling considerations – Contemporary Control Systems BASremote Installation Guide User Manual

Page 9

background image




TD040300-0II

9

C

ABLING

C

ONSIDERATIONS

When attaching cables to the BASR, Table 1 should be considered.

Function Signalling &

Data Rate

Minimum Required
Cable

Maximum
Segment Distance

Ethernet

10BASE-T
10 Mbps

Category 3 UTP

100 m (328 ft)

Ethernet

100BASE-TX
100 Mbps

Category 5 UTP

100 m (328 ft)

I/O

Unspecified

18 AWG

Unspecified

Expansion Unspecified

Belden

®

9841 or equivalent 100 m (328 ft)

Modbus

2.4–115.2 kbps Belden

®

9841, 3106A, 9842 100 m (328 ft)

Table 1 — Cabling Considerations

NOTE: If using shielded cable, connect to chassis at only one point. Wire
size may be dictated by electrical codes for the area where the equipment is
being installed. Consult local regulations.

Observe in Table 1 that 10BASE-T segments can successfully use Category 3,
4 or 5 cable — however, 100BASE-TX segments must use Category 5 cable.
Category 5e cable is highly recommended as the minimum for new installations.

The Ethernet port of the BASR employs Auto-MDIX technology so that either
straight-through or crossover cables can be used to connect to the network.