beautypg.com

3 remote installation to flow-bus, Remote installation to flow‐bus – Bronkhorst FLOW-BUS interface User Manual

Page 20

background image

BRONKHORST

®

 

Page 20   

 

 

 

 

FLOW‐BUS interface 

 

 

 

9.17.024 

4.1.3 Remote installation to FLOW‐BUS 

Some  FLOW‐BUS  modules  have  to  be  installed  on  the  bus  by  means  of  another  FLOW‐BUS  module  or  a  (personal) 
computer. This can be done as follows: 
 

 With a Readout/Control module, series E‐7000 or with a software program on the PC this new module can be 

searched. 

 The Readout/Control module or PC‐program will find the first free node‐address counted from address 3 (3 is 

first free address).  

 This free address number will be send to the new module, which should become active on this address. 
 After  a  reset  command,  also  send  by  the  Readout/Control  module  or  PC‐program,  the  new  module  will  be 

operational on the FLOW‐BUS system. 

 

 

Make sure to install only one new module at the same time. 

 
 

4.1.4 Install to bus on a pre‐defined node‐address or re‐address instrument on the bus 

In some applications it is necessary to put FLOW‐BUS devices on pre‐defined addresses because of the application 
software expecting this device on this address (e.g. PLC‐applications). This can be done as follows: 
(Install new module to the bus as described in the previous paragraphs.) 
 

 By means of the rotary switch on the instrument (if present). 
 By means of the micro‐switch on the instrument. See instruction manual 9.17.023. 
 By  means  of  the  special  menu  in  an  E‐7000  module  for  digital  instruments  it  is  possible  to  (re‐)  address 

instruments on the bus. 

 Go to the specific menu part and read the PNA (Primary Node Address) number. 
 Fill‐in the address you want the instrument to have on the bus. 
 The E‐7000 module will check if this address is already occupied by another instrument. If so, you could remove 

the other one and try again, or enter another address. 

 The module will restart and will get its new address from that moment on. 

 

 

Because it is not allowed in a FLOW‐BUS system to have 2 devices on the same node‐address, at 
(re)start of the instrument there will also be a check performed if its node‐address (in memory) is 
already occupied by another device. If so, the red LED will blink slowly. At that moment the module is 
not operational on the bus. You first have to re‐install it. The easiest way to do this is to press the micro 
push‐button on top of the instrument until the green LED starts blinking fast. After releasing the button 
the instrument will install itself on the bus automatically on a free address. When the green LED is 
burning continuously, the instrument is operational. 

 

 

If you take one or more modules out of your system, or if one or more modules do not get power, be 
careful installing new modules, or changing the configuration. This situation may occur if you take 
modules out for service. If you don’t change the configuration, you can replace your serviced 
instrument/module in your system without any problem. Mostly new modules will get the first free 
address, counted from address 3 (3 will be the first). This could be an address which should not be 
occupied (e.g. from a module which has been taken‐out for service). In that case install the new module 
and re‐address it as described, to avoid FLOW‐BUS communication problems. 

 

 

When connecting an instrument/module to the FLOW‐BUS, make sure that the instrument/module is in 
power‐off mode. After connection to the bus you can switch power on. At power‐up there will be a 
check to avoid the situation of two modules on the same bus address. This is important for error‐free 
bus‐communication.