beautypg.com

4 flow-bus installation and addressing, 1 installation, 2 automatic installation to flow-bus – Bronkhorst FLOW-BUS interface User Manual

Page 19: Flow‐bus installation and addressing, Nstallation, Automatic installation to flow‐bus, 4 flow‐bus installation and addressing

background image

BRONKHORST

®

 

4 FLOW‐BUS INSTALLATION AND ADDRESSING 

 

4.1 I

NSTALLATION

 

All modules in a FLOW‐BUS system must have their own address. FLOW‐BUS systems will not function properly when 
there are more modules on the same address. To avoid this, modules will do a check before getting operational on 
their bus‐address and give a message when this address is occupied. If you receive a complete FLOW‐BUS system from 
Bronkhorst all modules have been installed to the bus already (in one system). Each time you power‐up your system 
afterwards, the modules will start‐up on the same address on the bus, because these settings are stored in their non‐
volatile  memory.  So  if  you  receive  a  new  system,  normally  you  only  have  to  connect  the  cables  and  switch  on  the 
power. 
 

Page 19   

 

 

 

 

FLOW‐BUS interface 

 

 

 

9.17.024 

 

See document 9.17.023 for a more information. 
This document can be found at: 

http://www.bronkhorst.com/en/downloads/instruction_manuals/

 

 
If  a  new  module  has  to  be  connected  to  a  bus  system,  it  needs  a  free  address.  Normally  this  will  be  the  first  free 
address  counted  from  address  3.  Address  0  is  reserved  for  the  start‐up  procedure.  Address  1  is  reserved  for  an 
interface module to (personal) computers and address 2 has been reserved for operation modules like E‐7000.  There 
are four ways to add a new module to your bus system: 
 

4.1.1 Install to bus via rotary switches on the side of the instrument (if present). 

On the side of the instrument are rotary switches placed and a label with the 
explanation of the switches. Make sure to use a screwdriver which is suited 
for the switches. 
 
The switches have the following function: 
 
NODE ADDRESS (00 – 99) 
 
 
With the NODE ADDRESS switch, the instruments address can be set. The MSD is the high part of the decimal number 
and the LSD the low part. For instance address 25 means MSD on 2 and LSD on 5. 

 

The default switch position is 00. In this position the address is software programmable. 
The default software programmable address is 3. 

 
During instrument initialisation, the node address switches are read. If the switches specify a valid FLOW‐BUS address, 
i.e. a value from 3 to 99, this value is used. 
If the specified address differs from the value stored in the instrument, the new address is saved in memory. 
If the switches specify an invalid FLOW‐BUS address, i.e. a value of 1 or 2, the value stored in the instrument’s memory 
will be used as the address. 
 

4.1.2 Automatic installation to FLOW‐BUS 

Most FLOW‐BUS modules have the facility to install themselves automatically on the bus. This means that they are 
able to find the first free node‐address counted from 3 and connect themselves to the bus. This action can be started 
by  means  of  a  manual  interface  on  the  module.  Directly afterwards  the  new  module  will  be  part  of  the  FLOW‐BUS 
system. 
 

 

Make sure to install only one new module at the same time.