2 technical data, 3 basic function principles – BECKHOFF KL3681 User Manual
Page 8

Product overview
2.2
Technical data
Technical data
KL3681
KS3681
Number of inputs
1, voltage or current (1 A / 10 A)
Technology
digital multimeter with automatic range selection
Measured values
current, voltage (AC/DC)
Measuring voltage
300 mV, 3 V, 30 V, 300 V
Measuring current
100 mA, 1 A and 10 A via highcurrent path
Resolution
18 bit + sign in each measurement range
Internal resistance Measuring range DC 300 mV to
300 V
12,5 MΩ
Measuring range DC 100 mA to
1 A
0,2 Ω
Measuring range DC 10 A
3 mΩ
Measuring range AC 300 mV to
300 V
1 MΩ, ca. 33 pF
Measuring range AC 100 mA to
1 A
0,2 Ω
Measuring range AC 10 A
3 mΩ
Measuring error
0.01 % DC voltage measurement at 25°C
Measuring procedure
DC with arithmetic averaging,
AC with true RMS value calculation TrueRMS,
0...1 kHz input signal, Crest factor < 3 allowed
Update time
0.5 s, 1 s for measuring range selection
Electrical isolation
1500 V (terminal / Ebus)
Supply voltage for internal circuit
via KBus
Current consumption from via Ebus
typically 100 mA
Configuration
via KS2000 Configuration Software
Pluggable wiring
no
yes
Weight
approx. 70 g
Permissible ambient temperature temperature for
operation
0°C ... + 55°C
Permissible ambient temperature temperature for
storage
25°C ... + 85°C
Permissible Relative humidity
95 %, no condensation
Dimensions
approx. 15 mm x 100 mm x 70 mm (width aligned:
12 mm)
on 35 mm mounting rail conforms to EN 60715
Vibration / shock resistance
conforms to EN 6006826 / EN 60068227
EMC resistance burst / ESD
conforms to EN 6100062 / EN 6100064
Protection class
IP20
Installation pos.
variable
Approval
CE
2.3
Basic function principles
Features
The functionality of the KL3681 is similar to that of a commercial digital multimeter. The terminal offers the
following features:
• Singlechannel measurement
KL3681, KS3681
8