BECKHOFF KL3681 User Manual
Page 17

Mounting and wiring
Fig. 6: Terminal points of KL3681
Terminal point No.
Comment
V
1
Terminal point for voltage measurement (internally connected with terminal point 5)
COM
2
Ground (internally connected with terminal point 6)
10 A
3
Terminal point for current measurement, 10 A range
Shield
4
Shield (internally connected with terminal point 8)
V
5
Terminal point for voltage measurement (internally connected with terminal point 1)
COM
6
Ground (internally connected with terminal point 2)
1 A
7
Terminal point for current measurement, 1 A range
Shield
8
Shield (internally connected with terminal point 4)
WARNING
Danger for persons through electric shock!
For voltages greater than 25 V
AC
(42 V peak) or 60 V
DC
the fuse opening must be covered
by an additional terminal or the EL9011 end terminal. Risk of electric shock!
Attention
10 A branch is not fuseprotected
The current branch for 10 A is not fuseprotected. The device may be damaged if the cur
rent in the 10 A branch exceeds 10 A.
KL3681, KS3681
17
Version 2.0.0