R32.12 to r32.15, 35] value assignment of 1, R32.15 to r32.12 – BECKHOFF KL3681 User Manual
Page 35: 35] (default: 0x0000), Rp0.r32, 35]: 0x2804 (10244, Register page 0, R32: feature register

Access from the user programm
• If you write values into the user registers and have previously entered the user code word (0x1235) in
the code word register, these values are stored in the RAM registers and in the SEEPROM registers
and are therefore retained if the terminal is restarted.
The code word is reset with each restart of the terminal.
Register page 0
If register page 0 was selected with register R4 [
33], registers R32 to R63 have the following meaning.
R32: Feature register
The feature register specifies the terminal's configuration. Default: 0x2804 (10244
dec
)
Bit
R32.15
R32.14
R32.13
R32.12
R32.11
R32.10
R32.9
R32.8
Name
presentation
enFilter
enUserCalli
Bit
R32.7
R32.6
R32.5
R32.4
R32.3
R32.2
R32.1
R32.0
Name
frequency
enWdTimer
Bit
Name
Description
Default
R32.15 to
R32.12
presentation
0
dec
Left aligned (In left aligned presentation the extended
measuring range is not available!)
2
dec
1
dec
right aligned
2
dec
scaled: 1 bit per µV/µA
3
dec
reserved
4
dec
reserved
5
dec
float: Scaled presentation in floatingpoint format
6
dec
reserved
7
dec
reserved
R32.12
reserved
0
bin
R32.11
enFilter
0
bin
Filter not active
1
bin
1
bin
filter active
R32.10
enLimit2
0
bin
Threshold 2 is not active
0
bin
1
bin
Threshold 2 is active
R32.9
enLimit1
0
bin
Threshold 1 is not active
0
bin
1
bin
Threshold 1 is active
R32.8
enUserCalli
0
bin
User calibration not active
0
bin
1
bin
User calibration active
R32.7
frequency
0
bin
50 Hz mains frequency
0
bin
1
bin
60 Hz mains frequency
R32.6
reserved
0
bin
...
...
...
...
R32.3
reserved
0
bin
R32.2
enWdTimer
0
bin
Watchdog timer is not active
1
bin
1
bin
Watchdog timer is active (the watchdog is triggered if
no process data are received for 100 ms)
R32.1
reserved
0
bin
R32.0
reserved
0
bin
KL3681, KS3681
35
Version 2.0.0