Status byte (at register communication) – BECKHOFF KL3681 User Manual
Page 30
Access from the user programm
Bit
Name
Description
CB.7
RegAccess
1
bin
Register communication switched on
CB.6
R/W
0
bin
Read access
1
bin
Write access
CB.5 to CB.0
Register no.
Register number:
Enter here the number of the register [
31] that you wish
to read with input data word DataIN [
to write with output data word DataOUT [
28].
Status byte (at register communication)
The status byte (SB) is located in the input image [
28] and is transmitted from terminal to the controller.
Bit
SB.7
SB.6
SB.5
SB.4
SB.3
SB.2
SB.1
SB.0
Name
RegAccess
R/W
Register no.
Bit
Name
Description
SB.7
RegAccess
1
bin
Acknowledge for register access
SB.6
R
0
bin
Read access
SB.5 to SB.0
Register no.
Number of the register that was read or written.
KL3681, KS3681
30
Version 2.0.0