1-1. PURPOSE
1-2. OVERALL DESCRIPTION
1-3. SPECIFICATIONS
The Electronic Manual Voltage Control (MVC-301) is used as a back-up control device to provide
manual voltage control in case of voltage regulator failure. The unit can be mounted on a control
panel in ground vehicles, stationary equipment or shipboard locations.
The MVC-301 is a solid-state device enclosed in a metallic dark grey chassis and designed to be
'through-the-panel' mounted with the control accessible to an operator from the front of the panel.
A terminal strip located on the rear of the device facilitates installation and operation. An
AUTO-OFF-MANUAL voltage control mode switch is provided on the front panel.
Table 1-1 provides the electrical and physical specifications of the MVC 301.
Table 1-1. Specifications.
Input Power:
120 Vac, Single-Phase.
240 Vac, Single-Phase.
Output Adjustment
Range:
120 Vac Input:
240 Vac Input:
1 to 32 Vdc or 1 to 63 Vdc.
1 to 63 Vdc or 1 to 125 Vdc.
Watts Dissipated:
30 W maximum.
Minimum Residual
Voltage for Build-
up:
6 Vac.
Ambient Operating
Temperature:
-40
F (-40
C) to +158
F (+70
C)
Ambient Storage
Temperature:
-85
F (-65
C) to +212
F (+100
C)
Shock
Withstands up to 15 G's in each of three mutually perpendicular
axes.
Vibration:
Withstands the following:
5 - 27 Hz @ 1.3 G's,
27 - 52 Hz @ 0.036" double amplitude,
52 - 500 Hz @ 5 G's.
Weight:
3.0 lbs. (1.36 kg) net, 5 lbs. (2.26 kg) shipping.