Specifications, Power input – Basler Electric MVC236 User Manual
Page 21

9204300990 Rev J
15
Specifications
Power Input
Frequency
50 to 400 Hz, single-phase
Voltage Range
60 Vac Nominal:
45 to 70 Vac
120 Vac Nominal:
90 to 153 Vac
240 Vac Nominal:
170 to 305 Vac
Power Dissipation
85 W
Minimum Residual Buildup Voltage
10% of 60 Vac nominal input voltage or 5% of 120/240 Vac nominal input voltage.
Regulation
Accuracy
2% for a 10% change in input power and 5% for a 30% change in input power.
Temperature Stability
±5% for a 50
°C temperature change
Power Output
60 Vac Nominal Input
32 Vdc at 36 Adc, nominal. No less than 40 Vdc at maximum potentiometer setting.
120 Vac Nominal Input
63 Vdc at 36 Adc, nominal. No less than 79 Vdc at maximum potentiometer setting.
240 Vac Nominal Input
125 Vdc at 36 Adc, nominal. No less than 156 Vdc at maximum potentiometer setting.
Minimum Field Resistance
32 Vdc Nominal Output:
0.88
Ω
63 Vdc Nominal Output:
1.75
Ω
125 Vdc Nominal Output:
3.47
Ω
Physical
Temperature
Operating:
–40 to 70
°C (–40 to 158°F)
Storage:
–40 to 85
°C (–40 to 185°F)
Humidity
98% noncondensing, maximum
Shock
Withstands up to 15 G in each of three mutually perpendicular axes without any degradation of
performance.
MVC 236