Figure 5-5. type e sensing test connections -8, Figure 5-5 – Basler Electric BE1-32R User Manual
Page 80

NOTES
1. Type E sensing is calibrated in three-phase watts using single-phase sensing inputs. Using the test connections
shown, the relay may be calibrated in true three-phase power using one-half the pickup current that corresponds
to the desired overpower or underpower pickup in watts. Adjust the relay test set to produce this current value
from the following equation.
𝐼 = 0.5 ×
𝑊
𝑉
W is the desired pickup in watts.
V is the applied voltage.
I is the applied current.
With a wattmeter, W is determined by the following equation.
𝑊 = 2 × 𝑊𝑎𝑡𝑡𝑚𝑒𝑡𝑒𝑟 𝑅𝑒𝑎𝑑𝑖𝑛𝑔
2. Terminals 1 and 10 are the overpower trip output device connections for both BE1-32R and BE1-32O/U.
Terminals 2 and 10 are the underpower output connections for the BE1-32O/U.
3. Terminals 17 through 20 are auxiliary output contacts. Determine the auxiliary output contact configuration by
referring to the relay style number.
Figure 5-5. Type E Sensing Test Connections
5-8
BE1-32R, BE1-32O/U Testing
9171100990 Rev T