Figure 5-4. type d sensing test connections -7, Figure 5-4 – Basler Electric BE1-32R User Manual
Page 79

NOTES
1. Type D sensing is calibrated in three-phase watts using single-phase sensing inputs. Using the test connections
shown, the relay may be calibrated in true three-phase power using one-third of the pickup current corresponding
to the desired overpower or underpower pickup in watts. Adjust the relay test set to produce this current value
from the following equation.
𝑊 = 3 × 𝑉
𝐴
× 𝐼
W is the desired pickup in watts.
V is the applied voltage.
I is the applied current.
With a wattmeter, W is determined by the following equation.
𝑊 = 2 × 𝑊𝑎𝑡𝑡𝑚𝑒𝑡𝑒𝑟 𝑅𝑒𝑎𝑑𝑖𝑛𝑔
2. Terminals 1 and 10 are the overpower trip output device connections for both BE1-32R and BE1-32O/U.
Terminals 2 and 10 are the underpower output connections for the BE1-32O/U.
3. Terminals 17 through 20 are auxiliary output contacts. Determine the auxiliary output contact configuration by
referring to the relay style number.
Figure 5-4. Type D Sensing Test Connections
9171100990 Rev T
BE1-32R, BE1-32O/U Testing
5-7