Timing—continued, Accuracy, Power range (pickup) – Basler Electric BE1-32R User Manual
Page 23: Type tests, Dielectric strength, Surge withstand capability (swc), Timing—continued -13, Power range (pickup) -13, Type tests -13, Table 1-4. power pickup ranges -13

Timing—continued
Accuracy
Instantaneous:
<80 ms (60 Hz) or <100 ms, (50 Hz) up to a real power
magnitude of 2 times the setting
Definite:
±
5 percent or 50 ms, whichever is greater
Inverse:
+
5 percent or 50 ms, whichever is greater
NOTE: Operating time is repeatable within 2% or 50 ms
(whichever is greater) for any combination of time dial and power
settings within the specified operating temperature range.
Power Range (Pickup)
The power pickup range is adjustable over the ranges listed in Table 1-4.
Table 1-4. Power Pickup Ranges
Sensing
Input Type
Nom.
Volts Range
Switch Position (in watts)
A
B
C
D
E
F
G
H
J
K
A, B or V
1-phase
120
1
Hi 2.0
4.0
6.0
8.0
10.0 12.0 14.0 16.0 18.0
20.0
Lo 0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
2
Hi 20
40
60
80
100
120
140
160
180
200
Lo
5
10
15
20
25
30
35
40
45
50
3
Hi 100 200
300
400
500
600
700
800
900
1000
Lo 25
50
75
100
125
150
175
200
225
250
C, D, or E
3-phase
120
1
Hi 6.0 12.0 18.0 24.0 30.0 36.0 42.0 48.0 54.0
60.0
Lo 1.5
3.0
4.5
6.0
7.5
9.0
10.5 12.0 13.5
15.0
2
Hi 60
120
180
240
300
360
420
480
540
600
Lo 15
30
45
60
75
90
105
120
135
150
3
Hi 300 600
900 1200 1500 1800 2100 2400 2700 3000
Lo 75
150
225
300
375
450
525
600
675
750
A, B, or V
1-phase
208
or
240
4, 7 Hi 4.0
8.0
12.0 16.0 20.0 24.0 28.0 32.0 36.0
40.0
Lo 1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
5, 8 Hi 40
80
120. 160
200
240
280
320
360
400
Lo 10
20
30
40
50
60
70
80
90
100
6, 9 Hi 200 400
600
800 1000 1200 1400 1600 1800 2000
Lo 50
100
150
200
250
300
350
400
450
500
C, D, or E
3-phase
208
or
240
4, 7 Hi 12.0 24.0 36.0 48.0 60.0 72.0 84.0 96.0 108.0 120.0
Lo 3.0
6.0
9.0
12.0 15.0 18.0 21.0 24.0 27.0
30.0
5, 8 Hi 120 240
360
480
600
720
840
960 1080 1200
Lo 30
60
90
120
150
180
210
240
270
300
6, 9 Hi 600 1200 1800 2400 3000 3600 4200 4800 5400 6000
Lo 150 300
450
600
750
900 1050 1200 1350 1500
Type Tests
Dielectric Strength
Tested in accordance with IEC 60255-5 and IEEE C37.90. Withstands the following tests.
All circuits to ground:
2,121 Vdc
Input to output circuits:
1,500 Vac or 2121 Vdc
Surge Withstand Capability (SWC)
Qualified to IEEE C37.90.1-1989, Standard Surge Withstand Capability (SWC) Tests for Protective
Relays and Relay Systems
9171100990 Rev R
BE1-32R, BE1-32O/U General Information
1-13