Radio frequency interference, Shock, Vibration – Basler Electric BE1-32R User Manual
Page 24: Ul recognition, Gost-r, Temperature, Weight, Ul recognition -14, Gost-r -14, Temperature -14

Radio Frequency Interference
Maintains proper operation when tested for interference in accordance with IEEE C37.90.2-1987,
Standard Withstand Capability of Relay Systems to Radiated Electromagnetic Interference from
Transceivers.
Shock
In standardized testing, the relay has withstood 15 G in each of three mutually perpendicular planes
without structural damage or degradation of performance.
Vibration
In standardized testing, the relay has withstood 2 G in each of three mutually perpendicular planes, swept
over the range of 10 to 500 Hz for a total of six sweeps, 15 minutes each sweep, without structural
damage or degradation of performance.
UL Recognition
Recognized per Standard 508, file number E97033. Note: Output contacts are not UL recognized for
voltages greater than 250 volts.
GOST-R
GOST-R certified per the relevant standards of Gosstandart of Russia.
Temperature
Operating:
–
40°C to 70°C (–40°F to 158°F)
Storage:
–
65°C to 100°C (–85°F to 212°F)
Weight
S1 Configuration:
13.5 lb (6.12 kg) maximum
M1 Configuration:
18.5 lb (8.39 kg) maximum
1-14
BE1-32R, BE1-32O/U General Information
9171100990 Rev T