Type tests, Isolation, Surge withstand capability – Basler Electric BE1-50/51B-219 User Manual
Page 34: Radio frequency interference (rfi), Vibration, Shock, Environment, Agency recognition, Gost-r certification, Physical
![background image](https://www.manualsdir.com/files/773819/content/doc034.png)
28
9252000981 Rev J
Type Tests
Isolation
Meets IEC 255-5 and exceeds IEEE C37.90-2005, one-minute dielectric (high potential) tests as follows.
All circuits to ground:
2,828 Vdc or 2,000 Vac
Input to Output Circuits:
2,828 Vdc or 2,000 Vac
Surge Withstand Capability
Qualified to IEEE C37.90.1-2002 Standard Surge Withstand Capability (SWC) Tests for Protective Relays
and Relay Systems.
Impulse
Qualified to IEC 255-5.
Radio Frequency Interference (RFI)
Qualified to IEEE C37.90.2-2004.
Field-tested using a 5-watt, hand-held transceiver operating at random frequencies centered around 144
MHz and 440 MHz, with the antenna located 6 inches from the relay in both horizontal and vertical
planes.
Vibration
Withstands 2 G in each of three mutually perpendicular planes swept over the range of 10 to 500 Hz for a
total of 6 sweeps, 15 minutes each sweep.
Shock
Withstands 15 G in each of three mutually perpendicular planes.
Environment
Operating Temperature:
–40
°C to 70°C (–40°F to158°F)
Storage Temperature:
–50
°C to 70°C (–58°F to 158°F).
Agency Recognition
GOST-R Certification
GOST-R certified per the relevant standards of Gosstandart of Russia.
Physical
Weight:
6.1 lb (2.77 kg)
Specifications
BE1-50/51B-219/-226