Basler Electric BE1-50/51B-219 User Manual
Page 16

10
9252000981 Rev J
From the time characteristic curve equation:
K
BD
C
M
AD
T
N
Trip
+
+
−
=
(
)
028
0
2
02758
.
0
1
10
2
7624
7
0938
2
.
.
.
+
×
+
−
×
=
028
0
05516
.
0
1
10806
124
5248
15
.
.
.
+
+
−
=
seconds
0.209
=
From the reset characteristic curve equation:
1
M
RD
T
2
Reset
−
=
seconds
15.5
1
0
2
7.75
2
−
=
−
×
=
M = 0 if current goes to zero.
Negative result indicates reset time.
Results: Full trip = 0.209 seconds and full reset = 15.5 seconds if current goes to zero.
T
A
= 0.209 seconds (relay was at reset).
T
B
= value < T
A
because rewind has not gone to zero.
T
C
= value < T
A
because rewind has not gone to zero.
Figure 4. Coordination Timing Diagram
Installation
BE1-50/51B-219/-226