Basler Electric BE1-11 DNP3 Protocol User Manual
Page 57

9424200773 Rev A
51
Table 5. Analog Inputs
Analog Inputs
Static Object Number: 30
Change Event Object Number: 32
Request Function Codes Supported: 1 (read), 22 (assign class)
Static Variation Reported When Variation 0 Requested: User programmable. Default “variation 0” is 3
(32-bit Analog Input without Flag).
Change Event Variation Reported When Variation 0 Requested: User programmable. Default
“variation”) is 1 (32-bit Analog Change Event without Time).
Analog Input Deadband Object: 34
Point
Index
Description
Change Event Default
Assigned Class
0
Phase Bus Meter Circuit 1 VA Primary Magnitude
2
1
Phase Bus Meter Circuit 1 VA Angle
2
2
Phase Bus Meter Circuit 1 VB Primary Magnitude
2
3
Phase Bus Meter Circuit 1 VB Angle
2
4
Phase Bus Meter Circuit 1 VC Primary Magnitude
2
5
Phase Bus Meter Circuit 1 VC Angle
2
6
Phase Bus Meter Circuit 1 VAB Primary Magnitude
2
7
Phase Bus Meter Circuit 1 VAB Angle
2
8
Phase Bus Meter Circuit 1 VBC Primary Magnitude
2
9
Phase Bus Meter Circuit 1 VBC Angle
2
10
Phase Bus Meter Circuit 1 VCA Primary Magnitude
2
11
Phase Bus Meter Circuit 1 VCA Angle
2
12-13
Reserved
14
Phase Bus Meter Circuit 1 IA Primary Magnitude
2
15
Phase Bus Meter Circuit 1 IA Angle
2
16
Phase Bus Meter Circuit 1 IB Primary Magnitude
2
17
Phase Bus Meter Circuit 1 IB Angle
2
18
Phase Bus Meter Circuit 1 IC Primary Magnitude
2
19
Phase Bus Meter Circuit 1 IC Angle
2
20
Phase Bus Meter Circuit 1 V1 Primary Magnitude
2
21
Phase Bus Meter Circuit 1 V1 Angle
2
22
Phase Bus Meter Circuit 1 V2 Primary Magnitude
2
23
Phase Bus Meter Circuit 1 V2 Angle
2
24
Phase Bus Meter Circuit 1 3V0 Primary Magnitude
2
25
Phase Bus Meter Circuit 1 3V0 Angle
2
26
Phase Bus Meter Circuit 1 I1 Primary Magnitude
2
27
Phase Bus Meter Circuit 1 I1 Angle
2
28
Phase Bus Meter Circuit 1 I2 Primary Magnitude
2
29
Phase Bus Meter Circuit 1 I2 Angle
2
30
Phase Bus Meter Circuit 1 3I0 Primary Magnitude
2
BE1-11
Point List