Basler Electric BE1-11 DNP3 Protocol User Manual
Page 55

9424200773 Rev A
49
Table 4. Binary Output Status Points and Control Relay Output Blocks
Binary Output Status Points:
Object Number: 10
Variations supported: 1, 2
Request Function Codes supported: 1 (read)
Default Variation reported when variation 0 requested: 2 (Binary Output Status)
Control Relay Output Blocks
Object Number: 12
Variations supported: 1
Request Function Codes supported: 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, noack)
Point Index
Description
Control Operations
Off/Trip
On/Close
0
43-1 Operate
On/Off or Close/Trip
2
1
1
43-1 Operate
Pulse
0
3
2
43-1 Untag Blocking Tag
On or Close
0
2
3
43-1 Untag Informational Tag
On or Close
0
1
4
43-1 Tag Blocking Tag
On or Close
0
2
5
43-1 Tag Informational Tag
On or Close
0
1
6
43-2 Operate
On/Off or Close/Trip
2
1
7
43-2 Operate
Pulse
0
3
8
43-2 Untag Blocking Tag
On or Close
0
2
9
43-2 Untag Informational Tag
On or Close
0
1
10
43-2 Tag Blocking Tag
On or Close
0
2
11
43-2 Tag Informational Tag
On or Close
0
1
12
43-3 Operate
On/Off or Close/Trip
2
1
13
43-3 Operate
Pulse
0
3
14
43-3 Untag Blocking Tag
On or Close
0
2
15
43-3 Untag Informational
On or Close
0
1
16
43-3 Tag Blocking Tag
On or Close
0
2
17
43-3 Tag Informational Tag
On or Close
0
1
18
43-4 Operate
On/Off or Close/Trip
2
1
19
43-4 Operate
Pulse
0
3
20
43-4 Untag Blocking Tag
On or Close
0
2
21
43-4 Untag Informational Tag
On or Close
0
1
22
43-4 Tag Blocking Tag
On or Close
0
2
23
43-4 Tag Informational Tag
On or Close
0
1
24
43-5 Operate
On/Off or Close/Trip
2
1
25
43-5 Operate
Pulse
0
3
26
43-5 Untag Blocking Tag
On or Close
0
2
27
43-5 Untag Informational Tag
On or Close
0
1
28
43-5 Tag Blocking Tag
On or Close
0
2
29
43-5 Tag Informational Tag
On or Close
0
1
30
101 Operate
Close/Trip
1
2
31
101 Untag Blocking Tag
On or Close
0
2
32
101 Untag Informational Tag
On or Close
0
1
33
101 Tag Blocking Tag
On or Close
0
2
BE1-11