4
9424200773 Rev A
DEVICE PROFILE DOCUMENT
- IN1-4 is immediately asserted on startup.
- For Unsolicited Responses, if the number of maximum retries has been reached, the outstation
continues to transmit unsolicited responses with larger intervals (off-line intervals) indefinitely until
confirmation is received from the master.
Maximum Data Link Frame Size (octets):
Transmitted
292
Received 292
Maximum Application Fragment Size (octets):
Transmitted
configurable up to 4096
Received 1024
Maximum Data Link Re-tries:
None
Fixed at 2 (only if frame sent with confirm
requested)
Configurable
Maximum Application Layer Re-tries:
None
Fixed at
Configurable
Requires Data Link Layer Confirmation:
Never
Always
Sometimes
Configurable. Default is NEVER.
Requires Application Layer Confirmation:
Never
Always (not recommended)
When reporting Event Data
When sending multi-fragment responses
Timeouts while waiting for:
Data Link Confirm
None
Fixed at 3000 ms
Variable
Configurable
Complete Appl. Fragment
None
Fixed at _
Variable
Configurable
Application Confirm
None
Fixed at ___
Variable
Configurable.
5000 ms default
Complete Appl. Response
None
Fixed at _
Variable
Configurable
Sends/Executes Control Operations:
WRITE Binary Outputs
Never
Always
Sometimes
Configurable
SELECT/OPERATE
Never
Always
Sometimes
Configurable
DIRECT OPERATE
Never
Always
Sometimes
Configurable
DIRECT OPERATE - NO ACK
Never
Always
Sometimes
Configurable
Count > 1
Never
Always
Sometimes
Configurable
Pulse On
Never
Always
Sometimes
Configurable
Pulse Off
Never
Always
Sometimes
Configurable
Latch On
Never
Always
Sometimes
Configurable
Latch Off
Never
Always
Sometimes
Configurable
Queue
Never
Always
Sometimes
Configurable
Clear Queue
Never
Always
Sometimes
Configurable
Reports Binary Input Change Events when no
Reports time-tagged Binary Input Change Events
Device Profile Document