Link layer settings, Application layer settings, Time synchronization support setting – Basler Electric BE1-11 DNP3 Protocol User Manual
Page 18: Unsolicited response support settings, Objects default variations settings

12
9424200773 Rev A
Link Layer Settings
1.
Data Link Address (Device DNP address)
-
Range: 0 to 65519 (default address = 1)
2.
Data Link Layer Confirmation
-
Select between NEVER/SOMETIMES/ALWAYS (default is NEVER. DNP over Ethernet
should always be NEVER.)
Application Layer Settings
1.
Application response fragment size
-
Range: 240 to 4096 (default size = 2048)
2.
Application confirmation timeout
-
Range: 1 to 2678400000 ms (default value = 5000 ms)
Time Synchronization Support Setting
Time synchronization is disabled by default (setting value = 0). Time synchronization should always be
disabled for DNP over Ethernet. Range is from 0 to 2678400000 ms. DNP synch time will affect the
device time based on Time Priority Setup. If not selected in Time Priority Setup settings list (DNP Priority
= 0), DNP sync time will not be used to synchronize device time. Clock setup is configurable using
BESTCOMSPlus and the front panel interface.
Unsolicited Response Support Settings
1.
Unsolicited support DISABLED/ENABLED
-
The DNP Unsolicited Response Function should be “Disabled” for RS-485 applications
since there is no collision avoidance mechanism.
2.
Master Data Link Address (DNP Unsolicited Response Destination Address)
-
Range: 0 to 65519 (default address = 5)
3.
Unsolicited Response Confirmation Timeout in ms
-
Range: 0 to 2678400000 ms. When setting = 0, the value is the same as setting for
Application Confirmation Timeout.
4.
Number of unsolicited retries
-
Range: 0 to 255 (default = 2)
5.
Unsolicited off-line interval in ms
-
Range: 0 to 2678400000 ms (default = 10000 (10 seconds))
6.
Unsolicited response trigger conditions
-
Number of Class 1 events (range from 1 to 100)
-
Number of Class 2 events (range from 1 to 100)
-
Number of Class 3 events (range from 1 to 100)
Objects Default Variations Settings
1.
Default variation for Binary Input (Object 1)
-
Range: 1 or 2 (default = 1)
2.
Default variation for Binary Input Change (Object 2)
-
Range: 1 or 2 (default = 2 (with time))
3.
Default variation for Analog Input (Object 30)
-
Range: 1, 2, 3, 4, or 5 (default = 3 (32-bit without flag))
4.
Default variation for Analog Input Change (Object 32)
-
Range: 1, 2, 3, 4, 5, or 7 (default = 1 (32-bit without time))
DNP Settings
BE1-11