Basler Electric BE1-11 DNP3 Protocol User Manual
Page 14

8
9424200773 Rev A
OBJECT
REQUEST
(BE1-11 will parse)
RESPONSE
(BE1-11 will respond
with)
Obj.
Var.
Description
Function
Codes (dec)
Qualifier Codes
(hex)
Function
Codes
(hex)
Qualifier
Codes
(hex)
30
2
16-Bit Analog Input With
Flag
1 (read)
22 (assign class)
00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)
81
00,01 (start-
stop)
17,28 (index)
30
3
(default –
see notes
1, 2)
32-Bit Analog Input
Without Flag
1 (read)
22 (assign class)
00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)
81
00,01 (start-
stop)
17,28 (index)
30
4
16-Bit Analog Input
Without Flag
1 (read)
22 (assign class)
00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)
81
00,01 (start-
stop)
17,28 (index)
30
5
Short float analog input
1 (read)
22 (assign class)
00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)
81
00,01 (start-
stop)
17,28 (index)
32
0
Analog Change Event
(Variation 0 is used to
request default variation)
32
1
(default –
see notes
1, 2)
32-Bit Analog Input
without time
1 (read)
06 (no range)
07,08 (limited qty)
81
17,28 (index)
32
2
16-Bit Analog Input
without time
1 (read)
06 (no range)
07,08 (limited qty)
81
17,28
(index)
32
3
32-Bit Analog Input with
time
1 (read)
06 (no range)
07,08 (limited qty)
81
17,28
(index)
32
4
16-Bit Analog Input with
time
1 (read)
06 (no range)
07,08 (limited qty)
81
17,28
(index)
32
5
Short float analog
change event without
time
1 (read)
06 (no range)
07,08 (limited qty)
81
17,28
(index)
32
7
Short float analog
change event with time
1 (read)
06 (no range)
07,08 (limited qty)
81
17,28
(index)
34
0
(Variation 0 is used to
request default variation)
1 (read)
2 (write)
00,01 (start-
stop)
17,28 (index)
34
1
16-Bit Analog Input
Deadband
1 (read)
2 (write)
For read:
00,01,06,07,08,17,
28
For write:
00,01,07,08,17,28
81
00,01 (start-
stop)
17,28 (index)
34
2 (default)
32-Bit Analog Input
Deadband
1 (read)
For read:
00,01,06,07,08,17,
28
For write:
00,01,07,08,17,28
81
00,01 (start-
stop)
17,28 (index)
40
0
Analog Output Status –
(Variation 0 is used to
request default variation)
1
00,01 (start-stop)
06 (no range)
07,08 (limited qty)
17,28 (index)
40
1
32-bit Analog Output
Status
1 (read)
00,01 (start-stop)
06 (no range)
07,08 (limited qty)
17,28 (index)
81
00,01 (start-
stop)
17,28 (index)
Implementation Table