Installation, For qualified installers only) – Avalon Firestyles 564 HO GS2 Installation User Manual
Page 28
28
Installation
(
for qualified installers only)
28
Travis Industries
4150330
100-01408
Vent Configurations with Horizontal Termination (Dancing/DiamondFyre)
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and
diffuser positions.
Up to four elbows (45° or 90°) may be used.
Only one horizontal elbow may be used.
NOTE: With no vertical rise, LP installations have a maximum run of 2 feet (0.6m); NG installations have a
maximum run of 4 feet (1.2m).
5 feet (1.5m)
0 feet
20 feet (6m)
20 feet (6m)
10 feet (3m)
15 feet (4.5m)
0 feet
5 feet (1.5m)
10 feet (3m)
15 feet (4.5m)
20' max (6m)
10 feet (3m)
15 feet (4.5m)
21' max (6.4m)
21' max (6.4m)
Exhaust Restrictor # 5
2’ LP/4’ NG Maximum
Exhaust Restrictor #1
Intake Restrictor #1
Diffuser Position #1 (CLOSED)
Exhaust Restrictor #3
Intake Restrictor #2
Diffuser Position #2 (OPEN)
Exhaust Restrictor #4
Intake Restrictor #3
Diffuser Position #2 (OPEN)
Exhaust Restrictor #4
Intake Restrictor #5
Diffuser Position #2 (OPEN)
0 feet
5 feet (1.5m)
10 feet (3m)
15 feet (4.5m)
20' max (6m)
5 feet (1.5m)
0 feet
.
H1
H2
This is considered a horizontal
elbow (it does not matter
whether it turns right or left).
It may be a 90° or 45° elbow.
This is considered a vertical elbow.
Horizontal length (max. 24’) is calculated
by adding both lengths of horizontal run
(Horizontal Length = H1 + H2).