Installation
(
for qualified installers only)
26
Travis Industries
4150330
100-01408
Vent Configurations with Horizontal Termination (EmberFyre Burner only)
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and
diffuser positions.
Up to four elbows (45° or 90°) may be used.
Only one horizontal elbow may be used.
NOTE: With no vertical rise, LP installations have a maximum run of 2 feet (0.6m); NG installations have a
maximum run of 4 feet (1.2m).
5 feet (1.5m)
0 feet
20 feet (6m)
20 feet (6m)
10 feet (3m)
15 feet (4.5m)
0 feet
5 feet (1.5m)
10 feet (3m)
15 feet (4.5m)
20' max (6m)
15 feet (4.5m)
21' max (6.4m)
21' max (6.4m)
Exhaust Restrictor # 5
2’ LP/4’ NG Maximum
Exhaust Restrictor #1
Intake Restrictor #1
Diffuser Position #1 (CLOSED)
Exhaust Restrictor #2
Intake Restrictor #3
Diffuser Position #2 (OPEN)
Exhaust Restrictor #3
Intake Restrictor #3
Diffuser Position #2 (OPEN)
Exhaust Restrictor #4
Intake Restrictor #4
Diffuser Position #2 (OPEN)
5 feet (1.5m)
0 feet
5 feet (1.5m)
10 feet (3m)
0 feet
15 feet (4.5m)
20' max (6m)
10 feet (3m)
.
H1
H2
This is considered a horizontal
elbow (it does not matter
whether it turns right or left).
It may be a 90° or 45° elbow.
This is considered a vertical elbow.
Horizontal length (max. 24’) is calculated
by adding both lengths of horizontal run
(Horizontal Length = H1 + H2).