Installation – Avalon Firestyles 564 HO GS2 Installation User Manual
Page 22
22
Installation
(
for qualified installers only)
22
Travis Industries
4150330
100-01408
Approved Vent
May use 6-5/8” if terminated vertically.
Horizontal termination configurations use 8" (203mm) diameter Simpson Dura-Vent Model Direct-
Vent Pro (or GS)*.
* Other vent may be approved with this fireplace. Check with the vent manufacturer for details.
Vertical termination configurations use 8" (203mm) or 6-5/8" (168mm) diameter Simpson Dura-Vent
Direct-Vent Pro (or GS)*.
NOTE: When using 6-5/8” (168mm) diameter vent, make sure to accommodate the 4” (102mm)
clearance above the vent. Standard firestops do not include this clearance.
Always use the high-wind cap (58DVA-HC, 58DVA-VCH, or 46DVA-VCH).
Installation instructions for Simpson Dura-Vent may be found at
www.duravent.com
.
Other vents may be approved.
Vent Installation
Slide the vent sections together and turn 1/4 turn until the sections lock in
place.
Screws are not required to secure the vent. However, three screws may be
used to secure vent sections together if desired.
High temperature sealant is recommended at the appliance starter section
connection (use high-temperature silicone or Mill-Pac®).
If disassembly is required, at time of re-assembly check to see if the vent
creates a tight fit. If it does not, apply high temperature sealant to the joints
of the affected sections.
Horizontal sections require a 1/4" (6mm) rise every 12" (305mm) of travel
Horizontal sections require non-combustible support every three feet (e.g.: plumbing tape)
NOTE: Travis Industries strongly recommends using a 6-5/8” diameter vent when terminating
vertically.