beautypg.com

Introduction, The system, Safety features – Pinnacle Systems Universal Safety Controller HUB User Manual

Page 6: Specifications

background image

Page 1 of 18

Introduction

The Pinnacle Universal Safety Controller HUB (HUB) is a

control-reliable safety device that provides a convenient

way to run all safety and non-safety devices back to a

single point. The HUB combines 24 optically coupled

Inputs, 8 optically coupled solid-state Outputs for status, 2

Safety Relays with 3 N.O. (held closed) Dry Outputs, and

2 Safety solid-state N.O. (held closed) Outputs. Control-

Reliability is achieved by using redundant Input and

Output chains along with redundant CPU’s, but running

different software to cross check each other. Safety

Outputs are controlled via hardware watchdog timers as

well as both CPU’s, allowing either CPU to shut down the

Safety relays if a fault occurs.

The System

The Universal Safety Controller HUB (HUB) is a Din-Rail

mountable controller unit capable of being expanded (via

the CAN data network option) and monitored (via Ethernet

option). The HUB Din-Rail controller is 24vdc powered

and self contained with its own mechanical Safety Relays,

optically coupled inputs & outputs, function buttons for

control, and 2 line x 16 character Diagnostics display.

Safety Features

Two mechanical Safety Relays provide up to 3 dry N.O.

(held closed) ESTOP circuit outputs with 8A ratings.

2 Solid-State opto relays provide 2 +24vdc N.O. (held

closed) ESTOP circuit outputs with 1/2A ratings with

automatic resetting fuses that can drive 2 external Safety

relays (with external relay monitoring EDM).

Specifications

Input Power

24vdc +/- 20% (7watts max)

Fuse

Input: F1 1A slow-blo nano fuse

Output Channel D F2, F3 1/2A resetable

Relay Outputs

Channel C: PN# 32-098 3 pole 8A contact rating

Channel D: 1/2A Solid State opto with resetable fuse

(1A SS opto optional)

Status Outputs

Channel E: 1/2A Solid State resetable fuse

(1A SS opto optional)

Channel C4: 5A @250vac dry contact

(status for Channel C1-3)

Indicators

Diagnostics Display: 18-010 2 line x 16 character backlit

LCD

Channel C: Open (RED), Closed (GRN)

Channel D: Closed (GRN)

Mode: ON (Yel)

Construction & Dimensions

Din-Rail mountable polycarbonate housing providing

IP40 protection, UL94V-1

Internal RF shielding (nickel paint)

5.87” L x 2.95” W x 4.33”, 35.5mm (1.4”) din-rail mount-

ing

Environmental

0 to 50°C (up to 95% humidity, non-condensing)

Response Time

Note: Response time of the Universal Safety Control-

ler HUB (HUB) does not include response time of your

devices signalling this HUB.

Fault detection: 500uSec

Input device detection (open/closed): 500uSec per

device

Channel C: 5mSec open time

Channel D: <1mSec open time