The address of the receiver can be set up by the Address Switch - see picture above. The
BUTTON_ID sent by irCUE Receiver 485 to the control unit is a BUTTON_ID sent by IR wireless
control panel with an added OFFSET value. Button ID and OFFSET values are calculated according
to the formulas below.

BUTTON_ID (irCUE Receiver 485) = Offset + BUTTON_ID (IR wireless control panel)

Offset = 32 * ADDRESS

ADDRESS is binary coded by DIP switch in the range 0 to 255.

SW1 – ADDRESS bit 0

SW2 – ADDRESS bit 1

SW3 – ADDRESS bit 2

SW 4 – ADDRESS bit 3

SW 5 – ADDRESS bit 4

SW 6 – ADDRESS bit 5

SW 7 – ADDRESS bit 6

SW 8 – ADDRESS bit 7

ADDRESS of irCUE Receiver 485

OFFSET

SW1

SW2

SW3

SW4

SW5

SW6

SW7

SW8

0

0

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

1

32

ON

OFF

OFF

OFF

OFF

OFF

OFF

OFF

2

64

OFF

ON

OFF

OFF

OFF

OFF

OFF

OFF

3

96

ON

ON

OFF

OFF

OFF

OFF

OFF

OFF

...

255

8 160

ON

ON

ON

ON

ON

ON

ON

ON