Crompton Controls DCM User Manual
Page 55

54
Window Parameters
Emotron AB 01-2120-01r2
05
Measured line voltage.
Symbol V.
0 to 999 V
06
Measured peak power as per-
centage of the DCM measure-
ment range. Press - and + (in
this window) simultaneously
for 3 seconds to reset the
value.
Symbol %.
0 to 125%
0%
07
Total pumping time in hours.
Press - and + (in this window)
simultaneously for 3 seconds
to set the value to 0.
Symbol .
0-99999
0
08
Total number of pump starts.
Press - and + (in this window)
simultaneously for 3 seconds
to set the value to 0.
0-99999
0
09
Parameter lock.
Symbol . Is displayed when
parameter is locked.
0 to 999
11
Stop level. Symbol %.
0 to 125%
0%
12
Snore margin. Symbol %.
0 to 125%
4%
13
Type of Auto set. Auto set when
the pump is snoring (_)
(No liquid in the pit).
Auto set when the pump is not
snoring (
-
)
(Liquid in the pit).
(
-
) or (_)
(
-
)
Table 8
Window parameters and defaults
Window
Function
Value
Default
Custom
setting
Master Slave