4. Programming (continued)

2. Press and hold the left arrow key. On the main menu (―Detector Param‖ will be

showing), scroll right until the ―Ch1(sw) Set‖ menu appears on the DD-LCDHS
handset, and press ―on‖, then scroll left and right through the menu to see the
following parameters:


(Factory default settings are shown in brackets):
2.1 Switch level on
(9)

Lux level setting to prevent the luminaires being switched

on if the ambient light level is sufficient (adjustable

between 1 and 9). The luminaires will always be

switched on at level 9.


2.2 Switch level off (9)

Lux level setting to switch the luminaires off during

occupancy if the ambient light level goes above the

setting (adjustable between 1 and 9). Level 9 will always

keep the lights on. This must be set higher than the

―Switch level on‖, and it is recommended that it is a

minimum of 2 levels higher than (2.1) to avoid nuisance

switching.

Using the Programming Handset (Part No. DD-LCDHS)

Non-Dimming Lux Switching functions