7 /services/user/events.xml?begin=…?end=…?id, Services/user/events.xml?begin=…?end=…?id – CIRCUTOR PowerStudio Series User Manual
Page 27

PowerStudio
User Manual 27
Element: Registers from each of the harmonics
♦ harmonic: Harmonics number
♦ value: Harmonic value.
• Waveform value record
element>
…
id: Variable identifier (device.variable)
Element: Information from each of the points that make up the waveform
♦ msec: millisecond
♦ value: value
• EVQ event Record.
semicycleVoltage>
…
id: Variable identifier (device.variable)
value: Value of the event:
Phase: Phase in which the event occurs
duration:Duration of the event in milliseconds
averageValue: Average value:
previousValue: Old value
eventType: Type of event
♦ 0 Interruption
♦ 1 gap
♦ 3 Overvoltage
endForced: Mark if the event has finished correctly (F) or has be forced to
finalise (T)
semicycleVoltage: Each of the points that make up the semi-circular
effective voltage associated with the event. This field is optional and may not
exist.
♦ date: Date and time (DDMMYYYYHHMMSSUUU)
♦ value: Value
3.1.7 /services/user/events.xml?begin=…?end=…?id=…
Returns the events log of one or more events between dates “begin” and “end”. Each of the
events on which information is required must be included in the request as: